  • LMZW2-10.jpg

LMZW2-10


Model Code
L
M Z W 2 10
Encoding content
Current transformer
Busbar type
pouring type
With protection level
Reinforced
Design serial number
Outdoor LMZW2-10 type epoxy resin cast insulation busbar type fully enclosed current transformer, suitable for outdoor 12kV and AC 50/60Hz within the power measurement, current detection and relay protection.

Technical parameters


Rated primary current (A) Rated secondary current (A) Accurate Level Combination Capacity (VA) Rated short-time thermal current (kA/s) Rated dynamic stability current (kA)
600、800、1000 1(5) 1.0 15 100 250
1600、2000 1(5) 5P20 20 100 250

Products meet the standard GB20840.1, GB20840.2, IEC61869-1, IEC61869-2.

If users have special requirements, they can be determined after consultation with our company.

The above technical parameters are not the final technical commitment, please confirm our technical personnel shall prevail.

Product Information


Product Description

Outdoor LMZW2-10 type epoxy resin cast insulation busbar type fully enclosed current transformer, suitable for outdoor 12kV and AC 50/60Hz within the power measurement, current detection and relay protection.

Conditions of use

Installation location: outdoor.

Ambient temperature:-25 ℃ ~ 40 ℃, daily average temperature is not more than 30 ℃.

Altitude: ≤ 1000m, higher altitude can be selected as required.

Humidity: The maximum relative humidity at room temperature is 95%.

Pollution severity: Class IV.

There shall be no violent vibration or collision at the installation site.

The installation site is free of gas, steam, chemical deposition, explosion and corrosive media that seriously affect the insulation of the transformer.

Structural Overview

Busbar type, fully enclosed, epoxy resin cast insulated current transformer.

The primary terminal is identified as P2 and the secondary terminal is identified as S1-S2. This model has 2 secondary terminals and supports up to 1 secondary winding.

Technical Data

The electrical voltage of the equipment is 10kV, and the maximum operating voltage is 12kV.

1. power frequency withstand voltage of secondary winding and grounding 42kV/60s.

Power frequency withstand voltage between secondary windings and grounding 3kV/1min.

Lightning impulse withstand voltage 75 kV.

Other requirements shall be in accordance with GB20840.1, GB20840.2, IEC61869-1 and IEC61869-2.

Application Case


Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case