JSW-10WFR


JSW-10WFR

Model Code J S Z W 10 W F R
Encoding content
Voltage transformer
three-phase
epoxy resin cast insulation
Three-phase five-column type
Rated voltage
Outdoor
anti-resonance
With fuse protection
JSZW-10WFR type epoxy resin cast insulation fully enclosed voltage transformer, suitable for 12kV and AC 50/60Hz outdoor on-column switchgear for measuring instruments, meters, relays or other similar electrical energy metering or relay protection.

Technical parameters


Rated voltage (kV) Accurate Level Combination Rated output (VA) Thermal Limit Output (VA) Rated insulation level (kV) Rated frequency (Hz)
10/0.22,0.1 3.0/3P 500/50 400 12/42/75 50 or 60
10:√ 3 / 0.22:√ 0.1 3.0/3P 500/50

Note:

1. The products conform to GB20840.1, GB20840.3 and IEC61869-1, IEC61869-3.

2. The above form is not the final technical commitment, please confirm with our technical personnel.

Product Information


Product Description

JSZW-10WFR type epoxy resin cast insulation fully enclosed voltage transformer, suitable for 12kV and AC 50/60Hz outdoor on-column switchgear for measuring instruments, meters, relays or other similar electrical energy metering or relay protection.

Conditions of use

Installation location: outdoor.

Ambient temperature:-25 ℃ ~ 40 ℃, daily average temperature is not more than 30 ℃.

Altitude: ≤ 1000m, higher altitude can be selected as required.

Humidity: The maximum relative humidity at room temperature is 95%.

Pollution severity: Class IV.

There shall be no violent vibration or collision at the installation site.

The installation site is free of gas, steam, chemical deposition, explosion and corrosive media that seriously affect the insulation of the transformer.

Structural Overview

Fully enclosed, three-phase five-column, epoxy resin cast insulated voltage transformer.

The primary terminal is identified as A- B- C,0-N, and the secondary terminal is identified as a-b-c,0-n,da-dn. There are 7 secondary terminals in total, supporting 4 secondary windings.

Technical Data

The electrical voltage of the equipment is 10kV, and the maximum operating voltage is 12kV.

1. power frequency withstand voltage of secondary winding and grounding 42kV/60s, power frequency withstand voltage between secondary winding and grounding 3kV/1min.

Lightning impulse withstand voltage: 75kV

Other technical requirements shall be in accordance with GB20840.1, GB20840.3, IEC61869-1 and IEC61869-3.

Application Case


Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Key words:


Previous:

WOKEDA

Get Quote


We will be happy to provide you with quality products and services

Submit