  • JZW3-10R.jpg

JZW3-10R


Model Code
J
Z W 3 10 R
Encoding content
Voltage transformer
Pouring insulation
Outdoor type
Design serial number
Rated voltage class
With fuse protection
Outdoor JZW3-10R type epoxy resin casting insulation fully enclosed voltage transformer, suitable for outdoor 12kV and AC 50/60Hz power measurement, voltage detection and relay protection.

Technical parameters


Rated voltage (kV) Accurate Level Combination Rated output (VA) Thermal Limit Output (VA) Rated insulation level (kV) Rated frequency (Hz)
10/0.1 0.5 100 400 12/42/75 50~60
10/0.22 1.0 150 400 12/42/75
10/0.1,0.1 0.2/0.5 15/30 400 12/42/75
10/0.1,0.22 0.5/1.0 30/150 400 12/42/75

Note:

1. The product conforms to GB20840.1, GB20840.3 and IEC61869-1, IEC61869-3.

2. The above form is not the final technical commitment, please confirm with our technical personnel.

Product Information


Product Description

Outdoor JZW3-10R type epoxy resin casting insulation fully enclosed voltage transformer, suitable for outdoor 12kV and AC 50/60Hz power measurement, voltage detection and relay protection.

Conditions of use

Installation location: outdoor.

Ambient temperature:-25 ℃ ~ 40 ℃, daily average temperature is not more than 30 ℃.

Altitude: ≤ 1000m, higher altitude can be selected as required.

Humidity: The maximum relative humidity at room temperature is 95%.

Pollution severity: Class IV.

There shall be no violent vibration or collision at the installation site.

The installation site is free of gas, steam, chemical deposition, explosion and corrosive media that seriously affect the insulation of the transformer.

Structural Overview

Fully enclosed. Two-end insulation, epoxy casting insulation voltage transformer.

The primary terminal is identified as A- B, and the secondary terminal is identified as 1a-1b and 2a-2b. This model has 4 secondary terminals and supports 2 secondary windings.

Technical Data

The electrical voltage of the equipment is 10kV, and the maximum operating voltage is 12kV.

1. power frequency withstand voltage of secondary winding and grounding 42kV/60s.

Power frequency withstand voltage between secondary windings and grounding 3kV/1min.

Lightning impulse withstand voltage 75 kV.

Other technical requirements shall be in accordance with GB20840.1, GB20840.3, IEC61869-1 and IEC61869-3.

Application Case


Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case